This PAT testing kit includes everything you need to get started with PAT testing.
We also include the following additional accessories:
Part of the PAT400 series, the Megger PAT410 PAT Tester is from a new generation of downloading portable appliance testers.
With a high-duty cycle and a design tailored to fast testing, easy operation, and day-long use, this tester can perform in demanding situations
The Megger PAT 410 has a unique re-start function, designed for moving this piece of PAT equipment from one place to another, it will restart instantly from the same menu allowing the PAT technician to reduce testing time and become more productive.
With five soft keys, it gives the technician direct access to the most frequently used functions. The Megger PAT410 Portable Appliance Tester can perform the following tests; 250V and 500V insulation tests, 200mA, 10A, and 25A earth bond tests, differential, touch and alternative leakage tests, operational VA tests, RCD trip tests for portable RCDs, anti-surge and RCD protected extension leads and power cord testing.
The Megger PAT410 PAT machines provide a low profile 230V-only solution without the added weight required of 110V operation plus a database capacity for up to 10,000 test results.
To find out more about the PAT410 PAT Tester visit the Megger PAT410 product page.
Electrical Supply Range | 230V ±10 @ 50/60Hz |
Continuity Test (200mA) | |
Continuity Test Voltage | 9V AC ± 10% ± 0.1V (supply: 230V 50Hz) |
Continuity Resistance Accuracy | ±5% ± 3 digits (0 to 0.49Ω) ±5% ± 5 digits (0.5 to 0.99Ω) |
Continuity Resistance Resolution | 10mΩ (1 to 19.99Ω) |
Display Range | 0 to 19.99Ω |
Insulation Test (250V and 500V) | |
Insulation Resistance Accuracy (230V) | ±2% ±5 digits (0 to 19.99MΩ) ±5% ± 10 digits (20 to 99.99MΩ) |
Insulation Resistance Resolution | 0.01MΩ |
Display Range | 0 to 99.99MΩ |
Substitute Leakage Test | |
Test Voltage and Frequency | 40V AC ±10% nominal mains frequency |
Leakage Current Accuracy | ±5% ± 5 digits |
Leakage Current Resolution | 0.01mA |
Display Range | 0 to 19.99mA |
Differential Leakage Current | |
Test Voltage | Nominal mains 110/230V AC |
Test Frequency | Nominal mains 50/60Hz |
Differential Leakage Current Accuracy | ±5% ± 0.05mA (1.0mA to 9.99mA) ±5% ± 0.1mA (0.1mA to 0.99mA) |
Resolution | 0.01mA |
Display/Measurement Range | 0.10mA to 19.99mA |
Test Duration | User-selectable from 1 sec 10 sec to infinity |
Touch Current Test | |
Test Voltage and Frequency | Nominal mains supply |
Touch Current Accuracy | ±5% ± 5 digits |
Touch Current Resolution | 0.01mA |
Display | 0 to 10mA |
Operational Test | |
Test Voltage and Frequency | Nominal mains supply |
VA Rating | 230V 3700VA 110V 1800VA |
VA Accuracy | ±5% ± 10 digits (0 to 99VA) ±5% ± 50 digits (100VA to 999VA) ±5% ± 100 digits (1000VA to 3700VA) |
Resolution | 1VA (0 to 3700VA) |
Display Range | 0 to 3990VA |
Extension Lead Test | |
Tests Performed | Bond, insulation and polarity |
Polarity Test Voltage | 12V |
Polarity checks | Lead ok Live neutral S/C Live neutral reversed Live/neutral O/C |
Portable RCD Test | |
Test Voltage and Frequency | Nominal mains supply |
Test Current Accuracy | -8% to -2% (1/2 x I) +2 to +8% (1 x I, 5 x I) |
Trip Time Accuracy | ±1% ± 5 digits |
Trip Time Resolution | 0.1ms |
Display Range | 0 to 1999ms (1/2 x I) 0 to 300ms (1 x I) 0 to 40ms (5 x I) |
Fuse Test | |
Test Voltage | 3.3V |
Warning | Audible beep if fuse is OK |
Environmental | |
Operating Temperature | -10 to 50°C |
Storage Temperature | -20 to 60°C |
Humidity | 90% RH @ -10 to 30°C 75% RH @ +30 to 50°C |
Maximum Altitude | 2000m |
Ingress Protection | IP40 |
Other | |
Weight | 2.7kg |
Dimensions | 145 (H) x 255 (W) x 320mm (L) |
Safety | IEC 61010-1: CAT II 300V |
EMC | IEC 61326-1: 2006 IEC 61326-2-2: 2005 |