The Kewtech SMARTPAT PAT Tester – PAT Essentials Kit (Bundle 1) consists of the Kewtech SMARTPAT PAT Tester (supplied with Kewtech’s standard accessories) and an array of additional PAT testing accessories, such as labels, logbook and adapters. For a comprehensive overview of the items included in this bundle, please see the ‘What’s Included?’ section.
For further information regarding the Kewtech SMARTPAT PAT Tester, please see the following description.
The Kewtech SMARTPAT PAT Tester is a non-downloading, battery-operated PAT tester. It can be converted into a fully downloadable PAT tester when used in conjunction with the Kewtech KEWPAT App (NOT included).
This instrument is suitable for PAT testing extension leads, as well as Class I and Class II appliances with and without electronic on/off switches. To this end, it includes pre-programmed test sequences optimised for extension leads, and Class I and Class II appliances. These pre-programmed test sequences can be run via pressing the clearly labelled function buttons.
In addition to this, the Kewtech SMARTPAT PAT Tester can be used to perform the following portable appliance checks:
When the Kewtech SMARTPAT PAT Tester is used with the Kewtech KEWPAT App these tests may be arranged into personalised test sequences, allowing the user to tailor the SMARTPAT to his/her requirements.
Furthermore, as well as its suitability for testing extension leads, and Class I and Class II appliances, the Kewtech SMARTPAT PAT Tester is also optimised for checking 10mA and 30mA RCDs without tripping these components.
The Kewtech SMARTPAT PAT Tester is supplied with an array of accessories which facilitate the user’s ability to adapt the tester to perform the above tests. It is supplied with an EZYEARTH Earth Continuity Test Lead with Probe and Crocodile Clip, EZYLEAD Extension Lead Adapter, and EZYMAIN Mains Lead.
Adding to its extensive testing capabilities, the Kewtech SMARTPAT PAT Tester also includes a Test Lead Null setting for nullifying test lead resistance in order to attain accurate resistance measurements. Furthermore, it features an Appliance Pre-check in order to ascertain whether the instrument-under-investigation is powered on or off prior to commencing any checks. This function improves the safety of the Kewtech SMARTPAT PAT Tester and can be used to prevent damage to the instrument and the user.
Measurements and test results are indicated on the Kewtech SMARTPAT PAT Tester’s large, backlit display. Via this display, the user can view a written PASS or FAIL indication as well as a numerical measurement (where applicable). Moreover, the backlight will change colour in order to indicate whether a test has been passed or failed; this light will change to green to indicate a PASS and will change to red to indicate a FAIL.
As indicated above, the Kewtech SMARTPAT PAT Tester is a non-downloading, battery-operated portable appliance tester. It is capable of performing up to 1400 tests over the duration of its replaceable battery’s lifetime. The Kewtech SMARTPAT PAT Tester is an adaptable, comprehensive, and easy-to-use instrument.
For an overview of the additional items included in this kit, please see the following table.
Item Description | SMARTPAT PAT Tester – PAT Essentials Kit (Bundle 1) |
---|---|
Deluxe Carrying Case Keep all of your equipment safe and in one place with this large-size carrying case! (appearance of the case may vary depending on current stock) |
√ |
Need to check if your sockets are working right? Just plug this into a standard UK plug socket and if there's a problem, the socket tester will let you know about it! |
√ |
Gain a certificate of competency to carry out PAT testing in just two hours with our online PAT course and exam. Teams of staff may be trained by purchasing the course multiple times; each staff member will be assigned a unique activation code and login. |
√ |
Keep a record of all of your tests with our logbook. The book includes carbon-copied records, allowing you to keep one for yourself and give the other to customers or keep for a reference. |
√ |
When PAT testing, it's common practice to check microwaves are also not emitting high levels of radiation. With our microwave leakage detector, you'll be able to do this testing with ease. |
√ |
You'll need this adapter to connect your PAT tester to laptop/PC power leads and other similar equipment which has a cloverleaf-shaped connector. |
√ |
This adaptor is used to connect to laptop power supplies, portable projectors and other similar equipment. |
√ |
You'll find several appliances such as game consoles, laptop power supplies, audio/visual equipment and more use this type of connector - with this adapter, you can connect them up to your PAT tester. |
√ |
A handy set of insulated screwdrivers (suitable for live working to 1000V) suitable for a wide variety of applications. |
√ |
You'll need these every time an appliance passes a test - just tear one off, fill in the fields (appliance ID, your name, test date and next test due date) and stick on the appliance when done. |
√ |
These circular-shaped PAT labels are great for plug tops and any other appliance. The labels also include space for ticking the month/year the next test is due. |
√ |
These passed labels wrap around a wire/cable from an appliance and are recommended for use with power supplies or on appliances where you can't stick a label. They also include space for writing your appliance ID, name, test date and next test date. |
√ |
You won't need these as often as your passed labels, but you'll need to apply one of these whenever an appliance fails a test. If it does fail, the item should be taken out of service for repair or replacement |
√ |
The KEWPAT App is NOT included with the Kewtech SMARTPAT PAT Tester – PAT Essentials Kit (Bundle 1). However; it is required in order to transform the Kewtech SMARTPAT PAT Tester into a fully downloadable PAT tester, as well as facilitate the creation of personalised test sequences.
Please see the video and bullet points below for a quick introduction to the KEWPAT App. This app is available to download for free from the App Store (iOS) and Google Play (Android).
Specification | EZYPAT | EZYPAT PLUS | SMARTPAT |
200mA Continuity Test | X | X | X |
250V Insulation Test | X | X | X |
500V Insulation Test | X | X | X |
Substitute Leakage Test | X | X | X |
Polarity Check | X | X | X |
110V Load and Run Test | X | X | |
230V Load and Run Test | X | X | |
Portable RCD Test | X | ||
Compatible with KEWPAT App | X | ||
Customisable Test Sequences | X |
Protective Conductor Resistance Test | ||
Measuring range | 0.00 - 20.00 Ω (NULL value inc)* | |
Over-range indication | > 20.00 Ω | |
Resolution | 0.01Ω | |
Open-circuit voltage | 5 V ±0.4 V DC | |
Measuring current | 200 mA DC (nominal value) | |
Accuracy | ±3%rdg ±5dgt | |
* Resistances exceeding 3 Ω cannot be cancelled by NULL function | ||
Mains Voltage | ||
Display range | 30 - 270 V | |
Hi/ Lo indication | < 30 V: No voltage indication > 270 V: 270 V | |
Resolution & Accuracy | 1 V ±3%rdg ±5dgt | |
Insulation | ||
Rated Voltage | 250V | 500V |
Measuring range | 0.00 - 20.00 MΩ | |
Over-range indicatio | > 20.00 MΩ | |
Resolution | 0.01 MΩ | |
No-load voltage | 250 V DC +20%, -0% | 500 V DC +20%, -0% |
Short-circuit current | 1.5 mA DC or less | |
Rated current | 1 -1.2 mA with a load of 0.25 MΩ | 1 to 1.2 mA with a load of 0.5 MΩ |
Accuracy | ±2%rdg±3dgt | |
Substitute Leakage | ||
Measuring range | 0.10 - 12.00 mA rms | |
Over-range indication | > 12.00 mA | |
Resolution | 0.01mA | |
Open-circuit voltage/ Freq | 30 V ±5 V rms / 50 Hz ±5% | |
Measuring current | 1.2 mA AC ±0.5 mA (when measuring 12.00 mA) | |
Accuracy | ±3%rdg±5dgt | |
Insuyltation Test Between L-N | ||
Open-circuit voltage | 4.5 V ±0.5 V DC | |
Criteria of judgement | 100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted | |
Run Leakage | ||
Item | Load Current | Leakage Current |
Mains voltage range | 100 - 253 V / 50 Hz | |
Measuring range | 0.10 - 13.00 A rms | 0.10 - 20.00 mA rms |
Display range | 0.00 - 13.00 A | 0.00 - 20.00 mA |
Over-range indication | > 13.00 A | > 20.00 mA |
Resolution | 0.01A | 0.01mA |
Accuracy | ±10%rdg ±5dgt | ±3%rdg ±5dvgt |
Max. rating | 3 kVA max. / 15 sec. cont. | |
RCD Test | ||
Rated voltage | 230 V - 15% to +10% / 50Hz | |
Rated current | 10 mA / 30 mA | |
Test duration | ×1: 0.0 ms - 500.0 ms | ×5: 0.0 ms - 40.0 ms |
Test current accuracy | 2% - 8% | |
Operating time accuracy | ±2 ms ( 40 ms) ±8 ms (>40 ms) |