The Kewtech EZYPAT PAT Tester – PAT Essentials Kit (Bundle 1) consists of the Kewtech EZYPAT PAT Tester (supplied with the standard manufacturer’s accessories), and a selection of additional PAT testing accessories. Please see the 'What's Included?' section for a comprehensive overview of what is included in the Kewtech EZYPAT PAT Tester – PAT Essentials Kit (Bundle 1).
Please see the following description for further information regarding the Kewtech EZYPAT PAT Tester.
The Kewtech EZYPAT PAT Tester is a battery powered tester capable of performing up to 1400 tests over one battery life cycle. It is the entry-level model in Kewtech’s range of EZYPAT/SMARTPAT PAT Testers. As such it is optimised for performing manual dead tests on Class I and Class II appliances without electronic on/off switches. Like its sister products, the Kewtech EZYPAT PAT Tester can also check extension leads.
The Kewtech EZYPAT PAT Tester includes the following testing capabilities:
Pre-programmed test sequences for Class I and Class II appliances and extension leads can be performed automatically at a touch of the clearly labelled function buttons. The Kewtech EZYPAT PAT Tester also includes a Test Lead Null function which nullifies test lead resistance during insulation tests, thereby ensuring checks are conducted accurately.
In addition to the above tests, test sequences and functions, the Kewtech EZYPAT PAT Tester includes a number of features optimised to improve the safety of this instrument. For instance, as mentioned above the Kewtech EZYPAT PAT Tester includes a low current continuity test and 250V insulation test, making it IT safe. It also features an appliance status pre-check function, which allows the user to determine whether the appliance-under-investigation is powered on or off prior to conducting any checks.
Results (PASS or FAIL) are indicated on the Kewtech EZYPAT PAT Tester’s large, backlit display. This backlit display will turn green to indicate a PASS result and will turn red to indicate a FAIL result. This colour change, in addition to displayed numerical values and a written PASS or FAIL indication, ensures that the Kewtech EZYPAT is easy and uncomplicated to use.
Further to this, accessories supplied as standard with the Kewtech EZYPAT PAT Tester allow the user to adapt the instrument to suit the testing environment and/or to facilitate a number of testing capabilities. It is supplied with an extension lead adapter and an earth continuity test lead with a probe and a crocodile clip.
The Kewtech EZYPAT PAT Tester is an easy-to-use, reliable, ergonomic and lightweight tester. It is ideal for those requiring a simple PAT tester for checking extension leads, as well as Class I and Class II appliances without electronic on/off switches.
The Kewtech EZYPAT PAT Tester is also available in a second bundle, the Kewtech EZYPAT PAT Tester PAT Professional Kit (Bundle 2). Please see the table below for an overview of the items included in both this bundle and Bundle 2.
Item Description | EZYPAT PAT Tester - PAT Essentials Kit (Bundle 1) | EZYPAT PAT Tester - PAT Professional Kit (Bundle 2) |
---|---|---|
Deluxe Carrying Case Keep all of your equipment safe and in one place with this large-size carrying case! (appearance of the case may vary depending on current stock) |
√ | √ |
Need to check if your sockets are working right? Just plug this into a standard UK plug socket and if there's a problem, the socket tester will let you know about it! |
√ | √ |
Gain a certificate of competency to carry out PAT testing in just two hours with our online PAT course and exam. Teams of staff may be trained by purchasing the course multiple times; each staff member will be assigned a unique activation code and login. |
√ |
√ |
Keep a record of all of your tests with our logbook. The book includes carbon-copied records, allowing you to keep one for yourself and give the other to customers or keep for a reference. |
√ | √ |
When PAT testing, it's common practice to check microwaves are also not emitting high levels of radiation. With our microwave leakage detector, you'll be able to do this testing with ease. |
√ | √ |
You'll need this adapter to connect your PAT tester to laptop/PC power leads and other similar equipment which has a cloverleaf-shaped connector. |
√ | √ |
This adaptor is used to connect to laptop power supplies, portable projectors and other similar equipment. |
√ | √ |
You'll find several appliances such as game consoles, laptop power supplies, audio/visual equipment and more use this type of connector - with this adapter, you can connect them up to your PAT tester. |
√ | √ |
A handy set of insulated screwdrivers (suitable for live working to 1000V) suitable for a wide variety of applications. |
√ | √ |
You'll need these every time an appliance passes a test - just tear one off, fill in the fields (appliance ID, your name, test date and next test due date) and stick on the appliance when done. |
√ | √ |
These circular-shaped PAT labels are great for plug tops and any other appliance. The labels also include space for ticking the month/year the next test is due. |
√ | √ |
These passed labels wrap around a wire/cable from an appliance and are recommended for use with power supplies or on appliances where you can't stick a label. They also include space for writing your appliance ID, name, test date and next test date. |
√ | √ |
You won't need these as often as your passed labels, but you'll need to apply one of these whenever an appliance fails a test. If it does fail, the item should be taken out of service for repair or replacement |
√ | √ |
Keep a database of your PAT testing information on your PC and print reports with SimplyPats Manual software. Please note that this software is manual entry; you cannot download directly from the PAT tester and you will need to type in records by hand. |
- | √ |
Specification | EZYPAT | EZYPAT PLUS | SMARTPAT |
200mA Continuity Test | X | X | X |
250V Insulation Test | X | X | X |
500V Insulation Test | X | X | X |
Substitute Leakage Test | X | X | X |
Polarity Check | X | X | X |
110V Load and Run Test | X | X | |
230V Load and Run Test | X | X | |
Portable RCD Test | X | ||
Compatible with KEWPAT App | X | ||
Customisable Test Sequences | X |
Protective Conductor Resistance Test | |
Measuring Range | 0.00 - 20.00 Ω (NULL value inc)* |
Over-range Indication | > 20.00 Ω |
Resolution | 0.01Ω |
Open-circuit Voltage | 5 V ±0.4 V DC |
Measuring Current | 200 mA DC (nominal value) |
Accuracy | ±3%rdg ±5dgt |
* Resistances exceeding 3 Ω cannot be cancelled by NULL function. |
|
Insulation | |
Measuring Range | 0.00 - 20.00 MΩ |
Over-range Indication | > 20.00 MΩ |
Resolution | 0.01 MΩ |
No-load Voltage | 250V : 250 V DC +20%, -0% |
500V: 500 V DC +20%, -0% | |
Short-circuit Current | 1.5 mA DC or less |
Rated Current | 250V: 1 -1.2 mA with a load of 0.25 MΩ |
500V: 1 to 1.2 mA with a load of 0.5 MΩ | |
Accuracy | ±2%rdg±3dgt |
Substitute Leakage | |
Measuring Range | 0.10 - 12.00 mA rms |
Over-range Indication | > 12.00 mA |
Resolution | 0.01mA |
Open-circuit Voltage/ Frequency | 30 V ±5 V rms / 50 Hz ±5% |
Measuring Circuit | 1.2 mA AC ±0.5 mA (when measuring 12.00 mA) |
Accuracy | ±3%rdg±5dgt |
Insulation Testy Between L-N | |
Open-circuit Voltage | 4.5 V ±0.5 V DC |
Criteria of Judgement |
100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted. |
Physical Specifications | |
Safety |
IEC/EN61010-1 CAT II 300V-instrument |
EMC | EN61326-1, 2-2 |
Possible number of |
Approx. 1400 times |
Boxed Weight | 1.61Kg |
Boxed Dimensions (L x W x D) | 261 x 140 x 130mm |