Designed to speed up PAT testing procedures and give users easy access to all testing functions, Fluke's 6200 PAT tester is a rugged, reliable testing instrument that can be used to check all types of appliance and cables for electrical safety in compliance with the regulations of the IET Code of Practice.
A mid-range PAT tester, the Fluke 6200 combines together the functionality of an entry-level tester with several advanced features you won't find on those items. The first of these is built in memory, allowing the 6200 to store and download up to 100 individual testing records (no more writing things down in a logbook!). The 6200's design also makes PAT testing simpler than ever before - just plug in your leads, attach to an appliance and press a dedicated test button once to activate a test.
Suitable for use on both 230V and 110V appliances, the 6200 can be used in various environments ranging from offices to construction sites that use specific low voltage appliances. The PAT tester is capable of performing earth bond testing (at low and high currents), insulation up to 500V, leakage (PE current, touch current and substitute current), IEC lead tests, appliance power and load current testing and can also perform PELV (protective extra low voltage) testing.
Although heavier than some other PAT testers, the 6200 is still light enough to be easily ported from test to test and is uniquely designed to fit comfortably in the hands. A large size LCD screen relays back testing results and dedicated ports for mains plugs, probes and IEC leads are included to make connections as simple as possible. A set of diagrams on the front of the tester also give quick visual prompts showcasing how to connect up the different testing procedures.
Fluke 6200-2 PAT Tester Key Features
- Revamped for 2014 - now easier to use with additional functionality
- Each test is assigned to a specific button for easy one-touch testing activation
- Pre-set PASS/FAIL levels save time and effort when testing
- Large size backlit screen for use in all lighting conditions
- Single mains socket for direct appliance connection
- Separate IEC socket for connection of mains/extension leads
- Help diagrams on front of tester
- Integrated carrying handle
- Carries out earth bond, insulation and leakage testing
- Connects to external printer via serial port
- Polarity checks
What's Included?
- Fluke 6200-2 PAT Tester
- Quick Reference Guide
- Hard Carrying Case
- Test Lead
- Test Probe
- Crocodile Clip
- Mains Cord
Fluke 6200 PAT Testing Kits
For just a little bit extra, you get a whole lot with our exclusive Fluke 6200 PAT tester kits! Including all the accessories you'll need when PAT testing on a daily basis, these amazing value bundles include everything from labels to a training DVD allowing you to train staff to gain a certificate in PAT testing!
Just use the table below to see the difference between our kits:
Item Description | Fluke 6200-2 PAT Tester Essentials Kit (Bundle 1) | Fluke 6200-2 PAT Tester Professional Kit (Bundle 2) |
---|---|---|
Socket Tester Need to check if your sockets are working right? Just plug this in to a standard UK plug socket and if there's a problem, the socket tester will let you know about it! |
√ | √ |
PAT Testing Training DVD + Not yet trained as a PAT tester? With our training DVD, you can train yourself from the comfort of your own home or workplace! The DVD includes access to our online examination for one person (you can also purchase additional exams for other team members, if needed). |
√ |
√ |
The PASS Handbook of Portable Appliance Testing Everything you need to know about PAT testing is outlined in this comprehensive book. Inside, you'll find useful information, colour-coded sections, photographic examples and much more to help you PAT test on a daily basis. |
√ | √ |
PASS PAT Testing Logbook Keep a record of all of your testing with our logbook. The book includes carbon-copied records, allowing you to keep one for yourself and give the other to customers or keep for a reference. |
√ | √ |
Microwave Leakage Detector When PAT testing, it's common practice to check microwaves are also not emitting high levels of radiation. With our microwave leakage detector you'll be able to do this testing with ease. |
√ | √ |
PASSPTA21 - IEC (C13 Female) You'll need this adaptor to connect your PAT tester to laptop/PC power leads and other similar equipment which has a cloverleaf-shaped connector. |
√ | √ |
PASSPTA29 - IEC Plug (C14) This adaptor is used to connect to laptop power supplies, portable projectors and other similar equipment. |
√ | √ |
PASSPTA28 - IEC Plug (C14) You'll find several appliances such as game consoles, laptop power supplies, audio/visual equipment and more use this type of connector - with this adaptor, you can connect them up to your PAT tester. |
√ | √ |
CK Tools AV05050 5 Piece Insulated Screwdriver Kit A handy set of insulated screwdrivers (suitable for live working to 1000V) suitable for a wide variety of applications. |
√ | √ |
WM1 - 500 x Passed PAT Testing Labels You'll need these every time an appliance passes a test - just tear one off, fill in the fields (appliance ID, your name, test date and next test due date) and stick on the appliance when done. |
√ | √ |
WM6500 - 500 x Circular Passed PAT Testing Labels These circular-shaped PAT labels are great for plug tops and any other appliance. The labels also include space for ticking the month/year the next test is due. |
√ | √ |
WM12 250 - 250 x Cable Wrap Labels These passed labels wrap around a wire/cable from an appliance and are recommended for use with power supplies or on appliances where you can't stick a label. They also include space for writing your appliance ID, name, test date and next test date. |
√ | √ |
WM7 250 - 250 x Failed PAT Testing Labels You won't need these as often as your passed labels, but you'll need to apply one of these whenever an appliance fails a test. If it does fail, the item should be taken out of service for repair or replacement |
√ | √ |
SimplyPats Manual PAT Testing Software Keep a database of your PAT testing information on your PC and print reports with SimplyPats Manual software. Please note that this software is manual entry; you cannot download directly from the PAT tester and you will need to type in records by hand. |
- | √ |
- Essential Bundle (1,000 Labels & Logbook) - PAT-ESSENTIAL-BUNDLE, typically £77.98
- IT Bundle (3 x IEC Adaptors & Socket Tester) - PAT-IT-BUNDLE, typically £46.96
- Tolsen Tools 7-Piece Insulated Screwdriver Set - TS-9900012, typically £16.99
Fluke 6200 Technical Specifications
Test Specifications | The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75 % RH. | |
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C. | ||
The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2. | ||
Power-on Test | The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency. | |
Display Range | 90 V to 264 V | |
Accuracy at 50 Hz | ± (2% + 3 counts) | |
Resolution | 1 V | |
Input Impedance | > 1 MΩ // 2.2 nF | |
Maximum Input Mains Voltage | 264 V | |
Earth Bond Test (Rpe) | Display Range | 0 to 19.99 Ω |
Accuracy (After Bond Test Zeroing) | ± (2.5% + 4 counts) | |
Resolution | 0.01 Ω | |
Test Current | 200 mA AC -0% +40% into 1.99 Ω 25 A AC ± 20% into 25 mΩ at 230 V |
|
Open Circuit Voltage | > 4 V AC, < 24 V AC | |
Bond Test Zeroing | can subtract up to 1.99 Ω | |
Insulation Test (Riso) | Display Range | 0 to 299 MΩ |
Accuracy | ± (5% + 2 counts) from 0.1 to 300 MΩ | |
Resolution | 0.01 MΩ (0 to 19.99 MΩ) 0.1 MΩ (20 to 199.9 MΩ) 1 MΩ (200 to 299 MΩ) |
|
Test Voltage | 500 V DC -0% + 10% at 500 kΩ load | |
Test Current | > 1 mA at 500 kΩ load, < 15 mA at 0 Ω | |
Auto Discharge Time | < 0.5 s for 1 μF | |
Max. Capacitive Load | Operational up to 1 μF | |
Touch Current Test | Display Range | 0 to 1.99 mA AC |
Accuracy | ± (4% + 2 counts) | |
Resolution | 0.01 mA | |
Internal Resistance (via Probe) | 2 kΩ | |
Measuring Method | Probe* | |
Substitute Leakage Current Test | Display Range | 0 to 19.99 mA AC |
Accuracy | ± (2.5% + 3 counts) | |
Resolution | 0.01 mA | |
Test Voltage | 100 V AC ± 20% | |
Load/Leakage Test: Load Current | Display Range | 0 A to 13 A |
Accuracy | ± (4% + 2 counts) | |
Resolution | 0.1 A* | |
Load/Leakage Test: Load Power | Display Range 230 V Mains | 0.0 VA to 3.2 kVA |
Accuracy | ± (5 % + 3 counts) | |
Resolution | 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)* | |
Load/Leakage Test: Leakage Current | Display Range | 0 to 19.99 mA |
Accuracy | ± (4% + 4 counts) | |
Resolution | 0.01 mA* | |
PELV Test | Accuracy at 50 Hz | ± (2% + 3 counts) |
Overload Protection | 300 V rms | |
Warning Threshold | 25 V rms | |
*The appliance under test is energized at mains potential. |
Environmental Specifications |
|
Operating Temperature | 0 to 40 °C |
Relative Humidity | Non condensing < 10 °C 95% from 10 to 30 °C 75% from 30 to 40 °C |
Safety Specifications |
|
Safety Rating | Complies with EN61010-1 3rd edition |
CAT II, 300 V, pol 2 |
Mechanical & General Specifications |
||
Size | 200 mm (L) x 275 mm (W) x 114 mm (H) | |
Weight | 3.13 kg | |
Power Supply | 230 V +10 % -15 %, 50 Hz ±2 | |
Power Consumption (Tester) | 13 W typical (idle) 60 W max. during 25A Bond test |
|
Storage | Temperature | -10 to 60 °C |
Corrosion | 70 °C @ 95 % RH for 5 days max. | |
Operating Altitude | 0 up to 2000 m | |
Sealing | IP-40 (enclosure), IP-20 (connectors) | |
EMC | Complies with EN61326-1, portable | |
EMI Immunity | 3 V/m |
Reviews
SKU | FLUPT1 |
---|---|
Manufacturer Part Code | 4324466 |
Model No | 6200-2 |
Country of Origin | Romania |